Live chat
Support1-215-316-5893(Guest ID: 8058063)

ICM Controls ICM530 3-Phase Surge Protective Device, Delta 240VAC or Wye 120/208VAC

$133.10
Category:ICM Controls
Manufacturer:ICM Controls
SKU:ICM530
Product code:ICM530
Product available
ICM Controls ICM530 3-Phase Surge Protective Device, Delta 240VAC or Wye 120/208VAC
$133.10

General specs

  • Product codeICM530
  • ManufacturerICM Controls
  • SKUICM530

Dimensions

  • Dimensions4.30in x 4.10in x 2.30in
  • Weight1.10lb
  • Installation Manual
  • Specification Sheet
  • ICM530-Series Sheet
  • Warranty Information

ICM Controls ICM530 3-Phase Surge Protective Device, Delta 240VAC or Wye 120/208VAC


Description:


  • The ICM530 Series is 4 models of Type 1 and Type 2 three-phase Surge Protective Devices for three-phase Delta and three-phase Wye configurations. 

  • When a surge occurs, the ICM three-phase surge suppressor will absorb the surge up to the specified limitations of the device. 

  • ICM incorporates superior thermally protected metal oxide varistor technology into the three-phase surge suppressors, which allows for safe disabling of the surge elements when a surge exceeds the thermal limits of the device. 

  • There is a single status light on the controls which identifies operational status when illuminated. 

  • The ICM 3-phase surge suppressors can be installed as a Type 1 or Type 2 device for both indoor and outdoor applications.


General Features:


  • 3-Phase Surge Protective Device, Delta 240VAC or Wye 120/208VAC

  • Delta or Wye Configuration 

  • NEMA Type 4X watertight plastic enclosure for outdoor and indoor installation 

  • Green LED indicates surge protection present 

  • Easily connects to electrical panel or disconnect for indoor and outdoor applications 

  • UL Listed Type 1 or Type 2 SPD 


Specifications:


Service Voltage (3-Phase)

240 VAC Delta or 120/208 VAC Wye

Short Circuit Current Rating (SCCR)

200 kA

Nominal Discharge Current (In)

20 kA

Maximum Surge Current

150,000 amps

SPD Type

Type 1 (can also be used in Type 2 applications)

Surge Protection Technology

TFMOV

Input Power Frequency

50/60 Hz

Protection Mode

3 for Delta configuration

6 for Wye configuration (neutral tied to ground)

Maximum Continuous Operation Voltage (MCOV)

L-L

300 VAC 

L-N

(for Wye configuration only): 150 VAC

VPR

Delta L-L

1200 VAC

Wye L-L

1200 VAC

Wye L-N

700 VAC


Replaces: 


ABB

OVRHLDxx-120

ASCO

420120Y, 420240D

ERICO (Critec)

TDX50C120/208, TDX50C120/240D

Intermatic

AG2083C3, L5F13Y1DG1

Leviton

55208-ASA

Siemens

TPS3D, TPS3C

Square D

SDSA2040, SDSA2040D

Eaton

SP1-208Y

SP1-240D

SP2-208Y

SP2-240D


Dimensions:


Product Height (in.): 2.30”

Product Width (in.): 4.10”

Product Depth (in.): 4.30”

Unit Weight: 1.10 lbs.