EWC Controls DAPC Distributed Air Pressure Controller

EWC Controls DAPC Distributed Air Pressure Controller
General specs
- Product codeDAPC
- ManufacturerEWC Controls
- SKUDAPC
Dimensions
- Dimensions13.00in x 13.00in x 3.00in
- Weight2.30 lb
EWC Controls Distributed Air Pressure Controller
Description:
The model DAPC can monitor your HVAC system static pressure and the zone damper “Open & Close” commands from your EWC® Zone Controller.
When the static pressure gets too high, the DAPC will modulate “Float” any Closed zone dampers towards the Open position, in order to control the static pressure.
Use the DAPC’s default static pressure set-point (0.5”wc) or select a set-point from the menu.
If preferred, customize and let the DAPC “discover” the actual “non-zoned” static pressure of your HVAC system, and adopt that value as the static pressure set-point.
If you don’t have enough room to install a bypass, the DAPC is your best airflow management solution.
Zone Capacity:
Modulate 1, 2 or 3 large air zones with 24vac
Power Open / Power Close “Floating Point” motor actuators. eg, MA-ND5 or MA-15S.
Compatible Zone Controllers:
The DAPC is compatible with all 24vac zoning systems when genuine Ultra-Zone® model ND, URD or SID dampers are specified and installed. (MA-ND5 or MA15S motor actuators).
Round and/or Rectangular Dampers by zone:
All zone dampers in a building are usually the same type, either round or rectangular.
The DAPC can handle Round dampers on one zone and Rectangular dampers on another zone.
If both damper types exist on one or more zones, use the default “linear” setting rather than “round” or “rectangular”
Static Pressure Set-Point:
The DAPC default static pressure set-point is 0.5”wc. You can select your own set-point from a wide range (.15”wc to 1.50”wc).
If you prefer, the DAPC can “discover” the non-zoned static pressure of your HVAC system and adopt that value as the operating static pressure set-point.
Status LCD:
The liquid crystal display scrolls to show the HVAC system Static Pressure versus the Static Pressure Set-Point.
Real time damper position “Open, Closed or Floating” can be viewed by hitting the UP button.
All DAPC programming is viewed on the LCD screen.
4 Button LCD Programming:
Four buttons are provided below the LCD screen to access the DAPC menu, choose your settings and observe damper input and output position (status).
Non-volatile memory will retain your menu settings even after a prolonged power failure
Damper LED’s:
Three easy to observe LED’s labeled Zone 1, Zone 2 and Zone 3, provide “status” of which zone dampers are Open, Closed or Floating.
Green = Open, Red = Closed, Flashing Green/Red = Floating.
Intuitive Default Programming:
The DAPC comes pre-loaded with Default Operating Parameters (See Page 2, Table 1) for Zoned HVAC Systems.
Default Programming means less work for the Installer, but still allows fine tuning to optimize performance and achieve personal preference.
Simply decide which “large” zones you want the DAPC to modulate “float”, when the static pressure gets too high.
Select the zones you want to modulate:
The average zoned home has 2 or 3 zones.
Sometimes the percentage of airflow (cfm) required for each zone is roughly the same (50/50 or 60 /40). Quite often the airflow ratios are very different (80/20, 70/30, 60 /30/10).
Because large zones can handle periodic overflow (excess air) without over-conditioning, but small zones may not, the DAPC lets you select which zones are allowed to modulate and which cannot!
Both zones should modulate on a (60/40 or 50/50) two zone system, but only modulate the largest zone on a (80/20) two zone system.
Specifications:
Category | Control Panel |
UPC Code | 845484020997 |
Pallet Length | 40 |
Pallet Width | 48 |
Pallet Height | 72 |
Pallet Weight | 40 |
Carton Size | 13x13x3 |
Dimensions:
Product Height (in.): 3”
Product Width (in.): 13”
Product Depth (in.): 13”
Unit Weight: 2.5 lbs.